Home station  
Set as homepage Add to favorites    中文版 繁体 English
 
Testing to: Rolling Fire testing | Building Fire testing | Marine material | Aircraft material | Fire Resistance | Jet Fire | Other
   
User name:
Password:
Code:
   
Fire standard
RailwayMarineBusBuilding
Test method More>>
BS 476-6:1989+A1:2009 fire...
BS 476-7:1997 Classificati...
BS 476-20:1987 fire resist...
BS ISO 4589-2:2006-06
NF P 92-501: M classificat...
NF P 92-503: M classificat...
NF P 92-504: Speed of spre...
ASTM E 662: Smoke density ...
ASTM E 648 Flooring test
ASTM E 162: surface flamma...
 
Home   USA   ASTM E 662: Smoke density test
 

ASTM E 662: Smoke density test

ASTM E 662: Smoke density test

ASTM E 662:2009 Standard test method for specific optical density of smoke generated by solid materials

Smoke density (Ds) testing conducted in accordance with ASTM E 662. Sample in a sealed furnace, radiation heat is 2.5w/cm2 of Flaming combustion and non-flaming test modes. The test duration is 20 minutes. Recording the 4 minutes, 8 minutes, 20 minutes of maximum smoke density.

This test method is applied to NFPA130 fire performance testing part.

Test data requirements: Ds (1.5) ≤ 100 and Ds (4.0) ≤ 200

 


 Source:防火网  Addtime:9/2/2010 Hits:4779

 Previous: ASTM E 162: surface flammability of materials using a radiant heat energy source

 Next: ASTM E 648 : floor-covering systems using a radiant heat energy source
 
 
Home | Fire Test & Certification | Standard | News | Product | Exhibition | Flame retardant | On-line consultation | Contact us
Copyright © 2008-2024 Firete.com All Right Reserved
TEL:(+86)-25-8658 3475